Note: Applies when used in typical indoor ambient air.
Consult Telaire if other gases or corrosive agents are
part of the application environment.
CO2 Calibration Guarantee
Telaire is serious about minimizing maintenance, so
each single-channel sensor (T8100/T8300) comes with
a lifetime calibration guarantee. And each dual channel
sensor has a two-year calibration guarantee (T8200).
Calibration Interval
For T8100 and T8300 series, no calibration is required
due to ABC Logic. For T8200 series, annual calibration
is recommend for the best accuracy. However,
most applications using T8200 series could extend
the calibration interval. For the humidity sensor, no
calibration is required. Replacement humidity sensors
are available.
If a Telaire 8000 series single channel sensor drifts out
of calibration range, it can be sent back to Telaire for
a free factory calibration. Further information on the
guarantee is available on our website.
Ventostat wall mount dimensions
Sensor Accuracy & Field Calibration
CO2 ABC Logic Self Calibration
T8100 and T8300 single channel sensors employ the
patented ABC (Automatic Background Calibration) Logic
self-calibration system. ABC Logic virtually eliminates
the need for manual calibration in applications where
the indoor CO2 level drops to outside levels during
unoccupied periods (e.g. during evening hours). ABC
Logic is a special software routine in the sensor
that remembers the background readings for 14
consecutive evenings, calculates if there is a sensor
drift, and then corrects for it.
T8200 – Dual Channel
The T8200 dual channel sensor can be described as
a CO2 channel that measures gas concentration and
a reference channel that measures the sensor signal
intensity. The dual channel sensor performs periodic
self-calibrations using the reference channel. The self-
calibrations are approximately every 24 hours. During
the self-calibration the sensor ppm reading is frozen, it
will not react to changing CO2. The calibration time is
adjustable but nominally two minutes.
Telaire recommends periodic gas calibration depending
on the application accuracy requirements. While the
reference channel corrects for changes over time, a
field calibration using nitrogen gas or alternatively
ambient calibration will immediately restore the highest
level of accuracy. Refer to the calibration manual for
details.
With ABC Logic enabled, the sensor will typically reach
its operational accuracy after 25 hours of continuous
operation at a condition that is exposed to ambient
reference levels. Sensors will maintain accuracy
specifications with ABC Logic enabled, given that
it is at least three times in 14 days exposed to the
reference value and this reference value is the lowest
concentration to which the sensor is exposed.