Controlled Ventilation
Ventilation is an important part of maintaining a
comfortable, healthy, productive environment for
people. Improper ventilation can have a negative
impact on occupant health and performance, increase
the risk from litigation, and/or waste energy. Demand-
controlled ventilation using CO2 sensors prevents
energy losses from over-ventilation while maintaining
indoor air quality. The most energy savings potential
is in buildings where occupancy fluctuates during a
24-hour period. Numerous organizations now require
and/or recommend CO2-based ventilation control in
different commercial HVAC applications. Some utility
companies also offer rebates to building owners for
installing CO2 sensors.
Wall mount sensors are used to control a specific area
such as a conference room, classroom, meeting hall,
etc. The Telaire 8000 Ventostat series are easy to install
and have a clean, modern look that suits most indoor
environments.
Ordering Information
Examples:
T8100-D ABC Logic, display
T8100-D-BAC ABC Logic, display,BACnet
T8200-HD Dual channel, Humidity, Display
T8300-BAC ABC Logic, pitotot tube, BACnet
T8100-DB ABC Logic, display, black case
The Telaire 8000 Ventostat series is available in a
number of configurations. The primary configuration is
determined by the type of CO2 sensor included.
T8100 — uses a single channel sensor using Telaire
patented ABC Logic for lifetime calibration. Single-
channel sensors are used in spaces where there is not
full-time occupation (most applications).
T8200 — uses a dual-channel optical system and
three-point calibration process for enhanced stability,
accuracy and reliability. Used in applications where
there is full-time occupation 24 hours a day.
T8300 — uses a single channel sensor with pitot tube kit
for duct measuring of CO2. ABC Logic enabled.
Notes:
1. This product is intended to be used in occupied building
HVAC applications.
2. This product is not designed or intended for use in safety
critical functions.
T8 100, 200, 300
Humidity (H) Display (D) Color (B, W) Range (5P, 10P) BACnet (BAC)
T8
Note: Not all combinations are available, i.e., T8300 with humidity. Please see www.ventostat.com to see the latest
list of available part numbers.
Note: T8100-5P-R versions are conformally coated.
Black versions are for applications such as movie theaters
2