OVP circuit
(1)To avoid the miss operation of OVP
It is recommended to connect the capacitor between OVP
terminal and GND for avoiding the miss operation by the spike
noise.
The OVP terminal is connected with the sink current source
(~150µA) in IC when OVP does not operate,for absorbing the
leak current of the photo coupler in the application.
So the resistance between the OVP terminal and GND for leak-
cut is not necessary.
If the resistance is connected,the supply current at the OVP
reset supply voltage becomes large.
As the result,the OVP reset supply voltage may become higher
than the operation stop voltage.
In that case,the OVP action is reset when the OVP is triggered
at the supply voltage a little high than the operation stop
voltage.
So it should be avoided absolutely to connect the resistance
between the OVP terminal and GND.
To REG or Vcc
Vcc
5.6k
M51996A
OVP
GND
PHOTO COUPLER
Fig.21 Peripheral circuit of OVP terminal
(2)Application circuit to make the OVP-reset time fast
The reset time may becomes problem when the discharge time
constant of CFIN • (R1+R2) is long. Under such the circuit
condition,it is recommended to discharge the CVCC forcedly and
to make the Vcc low value;This makes the OVP-reset time fast.
(3)OVP setting method using the induced third winding
voltage on fly back system
For the over voltage protection (OVP),the induced fly back type
third winding voltage can be utilized,as the induced third
winding voltage depends on the output voltage.Fig.23 shows
one of the example circuit diagram.
MITSUBISHI (Dig./Ana. INTERFACE)
M51996AP/FP
SWITCHING REGULATOR CONTROL
TO MAIN
TRANSFORMER
R1
Vcc
~
CFIN R2 Cvcc M51996A
GND
THE TIME CONSTANT OF
THIS PART SHOULD BE SHORT
Fig.22 Example circuit diagram to make the
OVP-reset-time fast
Vcc
M51996A
OVP
470
CVcc
GND
MAIN
TRANSFORMER
THIRD
WINDING
FIG.23 OVP setting method using the induced
third winding voltage on fly back system
(4)Method to control for ON/OFF using the OVP terminal
You can reset OVP to lower the OVP terminal voltage lower
than VTHOVPL.
So you can control for ON/OFF using this nature.
The application is shown in Fig.24.
The circuit turns off by SW OFF and turns on by SW ON in this
application.
Of course you can make use of the transistor or photo-transistor
instead of SW.
REG
5.1k
SW
M51996A
ON/OFF
FIG.24 Method to control for ON/OFF using the
OVP terminal