BCBD28-16-014S10 データシートの表示(PDF) - Cooper Bussmann, Inc.

部品番号
コンポーネント説明
一致するリスト
BCBD28-16-014S10
COOPER
Cooper Bussmann, Inc. COOPER
BCBD28-16-014S10 Datasheet PDF : 1 Pages
1
BCBD Series with Integrated Disconnect
Features
• ETL Listed to UL1741 Standard
• cETL Certified to CSA Standard C22.2 No. 29
• 28, 55, 75, 150 and 245A Integrated disconnect switches
• 4 to 24 Input circuits
• Continuous duty rated at 600Vdc
• 600Vdc Midget fuses* for overcurrent protection
• Finger-safe Cooper Bussmann modular fuse holders**
• Configured for both positive and negative grounded arrays
• Single or dual 90°C output terminals
• Negative input terminal blocks
• Steel or fiberglass NEMA 3R, 4 or 4X enclosures with seamless door gaskets
• Operating temperature -40°C to 50°C
• Common configurations in stock for fast shipment***
BCBD Series Integrated Disconnect Box
Disconnect Rating (Amps)
Number of input circuits
Input conductor range
Number of output conductors
Output conductor range
Max fuse size
Steel enclosure dimensions (in), weight
Fiberglass enclosure dimensions (In), weight
28A
4
4-14AWG
1 or 2
2/0-14AWG
30A
12x10x6, 15 lbs
14x12x6, 12 lbs
Specifications
55A
4
4-14AWG
1 or 2
2/0-14AWG
30A
12x10x6, 15 lbs
14x12x7, 12 lbs
75A
4 to 12
4-14AWG
1 or 2
350kcmil-6AWG
30A
20x20x6, 42 lbs
20x16x8, 28 lbs
150A
4 to 24
4-14AWG
1 or 2
350kcmil-6AWG
6A to 30A††
20x20x6, 50 lbs, or
20x24x6, 50 lbs
24x20x18, 35 lbs, or
24x24x10, 35 lbs
245A
4 to 24
4-14AWG
1 or 2
350kcmil to 6AWG
10A to 30A††
24x24x6, 55 lbs
24x24x8, 40 lbs
Part Number System Combiner Box with Disconnect Part Number System
Example: BCBD150-12-10F = _B _C _B _D _1 _5 _0 - 1_ 2_ - 1_ 0_ F_ S_ 0_ 6_ R_
Series Prefix BCBD – Combiner Box w/ Disconnect
Disconnect Ampacity 28 55 75 150 245
Number of Poles 04 08 12 16 20 24
Fuses (Amps)‡‡ 00 – No Fuses Included 01 02 03 04
05 06 08 09 10 12 15 20 25 (see Max fuse size in table)
Enclosure R – NEMA 3/3R
4 – NEMA 4 (Powder Coated Steel)
F – NEMA 4X (Fiberglass)
Surge Protective Device (SPD) S06 - 600Vdc
S10 - 1000Vdc
SPD Remote Contact Signaling R - With remote signaling
Blank - no remote contact
* See Data Sheet 2038 (DCM) or 2020 (KLM) for details.
** See Data Sheet 2053 for details.
*** Please verify stocked configurations with your Cooper Bussmann sales representative.
Certain specifications may be modified to meet requirements, please consult factory.
†† Depends on the number of input strings:
- BCBD150 (ckt/max A): 4/30A, 8/15A, 12/12A, 16/8A, 20/6A, 24/6A
- BCBD245 (ckt/max A): 4/30A, 8/30A, 12/20A, 16/12A, 20/12A, 24/10A
‡ Total system ampacity (poles x fuse amp rating) may not exceed ampacity of selected disconnect switch.
‡‡ When fuses are specified, 600Vdc midget fuses are installed in holders.
Typical Layout
Integral Disconnect on
BCBD Series
4 to 24 Circuits
BCBD245-24-00R Pictured
1210 BU-SB101341
Page 3 of 6