AC/DC Rectifier/Front End
500 Watts
CDP500 Series
XPiQ inc.
Intelligent Design Quality Product
• 1U Horizontal or 2U High Vertical Chassis
•
Y Measures only 10.2” x 3.4” x 1.65”
INAR •
ELIM Universal Input with Active PFC
PR 2003 •
Q3 Optional 1U High 19” Rack for
Hotswap/Redundant Operation
•
International Safety Approvals & CE Mark
Specification
Input
Input Voltage
•
Input Frequency
•
Power Factor
•
Harmonic Current •
Inrush Current
•
Input Protection
•
Input Current
•
Output
Output Voltage
•
Output Power
•
Output Voltage Adj. •
Minimum Load
•
Line Regulation
•
Load Regulation
•
Ripple & Noise
•
Transient Response •
Temperature
•
Coefficient
Hold Up Time
•
Remote Sense
•
Overvoltage
•
Protection
Overcurrent
•
Protection
Overtemperature
•
Protection
Current Sharing
•
Remote ON/OFF
•
General
90-264 VAC
Efficiency
• 87% typical at full load & 230 VAC
47-63 Hz
MTBF
• 200,000 demonstrated
0.95 A minimum
Meets EN61000-3-2
Limited to 20 A peak
Internal 10 A fuse
4.9 A at 120 VAC
2.8 A at 208 VAC
Isolation Voltage
Signals
LED Indicators
• 3000 VAC Input to Output
1500 VAC Input to Ground
500 VAC Output to Ground
• PSU enable, AC fail, DC OK,
global inhibit, overtemp &
output current readout
• DC Good
Size
• 10.2” x 3.4” x 1.65”
-54 VDC
Weight
• 2.9 Ibs (1.3 kgs.)
500 Watts
-40 to -59 VDC programmable
0 minimum load for all outputs
±0.1% maximum
±0.5% maximum
Environmental
Operating
•
Temperature
Cooling
•
-20 °C to +70 °C, derate linearly from
100% at +55 °C to 50% at +70 °C
Internal ball bearing fans with front
to back airflow
300 mV pk-pk maximum
Humidity
• 30-95% RH, non-condensing
3% max deviation, 500 µs
recovery time for a 25% load change
0.02%/°C
Storage Temperature •
Shock & Vibration •
-40 °C to +85 °C
IEC68-2-27, 2-64 & Mil-STD-810E, 20G,
Telecordia GR-63-CORE,
GR-487-CORE
>20ms minimum
Altitude
• Operation to 7,382 feet (2250m)
Up to 0.25 V compensation
-59.5 to -60.0 VDC
recycle input to reset
120% with auto recovery
Logic high signal for overtemp
conditions
EMC & Safety
Safety Approvals
•
EMI/EMC
•
Immunity and Surge •
UL1950. CSA C22.2 No 950,
EN60950 CE Mark LVD
EN61000-3-2, -3, EN55022 and FCC
20780 part 15J Class B conducted
Meets EN61000-4-2, -3, -4, -5, -6, -11
Single wire with ±10% accuracy
Standard * Preliminary datasheet - see website for current specs
•
www.XPiQ.com
PH: 508 429.9883
•
FAX: 800 226.2100
Email: sales@xpiq.com
Holliston, MA 01746 USA