AC/DC Front End
800 Watts
ZC8 Series
XPiQ inc.
Intelligent Design Quality Product
•
Hot Swap or Chassis Mount
Front End Switcher
•
Optional 3 Bay / 1U High Rack for
Hot-Swap 2+1 Redundant Operation
•
Active PFC - Meets EN61000-3-2, -3
•
World Wide Safety Approvals & CE Mark
•
OR’ing Diodes Standard on all Models
•
Single Wire Current Share
Specification
Input
AC Input Voltage
Input Frequency
Power Factor
Inrush Current
Input Protection
• 85-264 VAC
• 47-63 Hz
• 0.99
• Limited to 30 A peak
• Internal 20 A fuse
Output
Output Voltage
•
Output Power
•
Output Voltage
•
Adjustment
Minimum Load
•
Line/Load Regulation •
Ripple & Noise
•
Transient Response •
Temperature
•
Coefficient
Hold Up Time
•
Remote Sense
•
Overvoltage
•
Protection
Overcurrent
•
Protection
Overtemperature
•
Protection
Current Sharing
•
12, 24 or 48 VDC with 5 VSB
at 250 mA
650-800 W
±5% min
No minimum load for all outputs
±2%
1% pk-pk maximum
4% max deviation, 300 µs recovery
time for a 25% load change
0.02%/°C
20 ms minimum
Up to 0.25 V compensation
Latched shutdown, recycle
input to reset
Standard with auto recovery
Logic high signal for overtemp
conditions
±10%
General
Efficiency
MTBF
Isolation Voltage
Signals
LED Indicators
Size
Weight
• 75-85% typical at full load
• 200,000 hrs per Bellcore
• 3000 VAC Input to Output
1500 VAC Input to Ground
500 VAC Output to Ground
• DC OK = Logic Low
AC Fail = Logic High
Global Inhibit = Logic Low
Enable = Logic Low
Overtemp = Logic Hi
• 2 status indicators
• 5.0” x 10.0” x 1.6”
• 2.9 lbs. (1.3 kgs.)
Environmental
Operating
•
Temperature
Cooling
•
Humidity
•
Storage Temperature •
0°C to +70 C, full power to +50 °C
derate from +50 °C to 70 °C
at 2.5%/°C
Internal ball bearing fans
<95% RH, non-condensing
-40 °C to +85 °C
EMC & Safety
Safety Approvals
•
EMC
•
Immunity & Surge •
UL1950, CSA C22.2 No 950,
EN60950 CE Mark LVD
EN61000-3-2, -3, EN55022 and FCC
20780 part 15J Class B conducted
Meets EN61000-4-4, -5
•
www.XPiQ.com
PH: 508 429.9883
•
FAX: 800 226.2100
Email: sales@xpiq.com