Electrical Specs
Input
Input voltage
Frequency
Inrush current
Efficiency
Power factor
Turn-on time
EMI filter standard
EMI filter
(low leakage option)
Leakage current standard
Leakage current
(low leakage option).
Radiated EMI
Holdover storage
AC OK
Harmonic distortion
Isolation
Global Inhibit/Enable
Input fuse (internal)
Warranty
85-264 VAC
120-350 VDC
47-440 Hz
40 A peak max. (soft start)
70-80% typ. @ full case load
0.99 typ. meets EN61000-3-2
AC on 1.5 sec typ.,
Inhibit / Enable 150 ms typ.
CISPR 22
EN55022 Level “B”
CISPR 22
EN55022 Level “A”
2.0 mA max. @ 240 VAC
300 μA max. @ 240 VAC
CISPR 22
EN55022 Level “B”
20 ms minimum
(independent of input VAC)
>5 ms early warning min.
before outputs loose regulation
Full cycle ride thru (50 Hz)
Meets EN61000-3-2
Meets EN60950
TTL, Logic “1” and Logic “0”
MP4: 10 A
MP6: 15 A
MP8: 20 A
MP1: 20 A
2 years
Output
Adjustment range
Margining
Overall reg
Ripple
Dynamic response
Recovery time
Overcurrent protection
Short circuit protection
Overvoltage protection
(measured at sense
connection)
Reverse voltage protection
Thermal protection
Remote sense
100
80
%
Rated
60
Total
Case
Load
40
20
Power Derating Curve
50
Single wire parallel
DC OK
Minimum load
Normal Housekeeping bias voltage
Air Flow
Module inhibit
50
Switching frequency
Output/Output isolation
VME signal option board
Hold-up module (HUP)
30 35 40 45 50 55 60 65 70
TA – Ambient Temperature – °C
±10% min. all outputs
±4-6% nom.1
0.4% or 20 mV max.
(36 W modules 4% max.)
RMS: 0.1% or 10 mV, whichever is greater
Pk-Pk: 1.0% or 50 mV, whichever is greater
Bandwidth limited to 20 MHz
<2% or 100 mV, with 25% load step.
To within 1% in <300 μsec.
Single, main of dual output module
105-120% of rated output current.
Aux output of dual output module 105-140%
of rated output current.
Triple output module internally protected
Protected for continuous short circuit
Recovery is automatic upon removal of short.
Single output modules
2-5.5 V 122-134%
6-60 V 110-120%
Dual output module
2-6 V 122-134%
8-28 V 110-120%
Triple output module.
No overvoltage protection provided. Recycle
the AC input voltage to reset OVP circuit
100% of rated output current
All outputs disabled when internal temp
exceeds safe operating range. >5 ms warning
(AC OK signal) before shutdown
Up to 0.5 V total drop (not available on triple
output module)
Current share to within 2% of total rated current2
-2% to -8% of nominal for any monitored output2
Not required on single or triple output modules.
10% required on main of dual output modules3
5 VDC @1.0A mA max. present whenever AC
input is applied
TTL, isolated, singles and dual
(both outputs) only
250 kHz
>1 Megohm
POR signal & quad external DC OK
1-slot module providing an additional
34mSec (60mSec total)
hold-up @ 600W loading.
Notes:
1. Single output modules only.
2. Single and main of dual output modules only.
3. Contact factory for optional preload if required.